2021 IPC Chapter 6
Chapter 6 of the 2021 IPC answers a simple question: will water reach every fixture at a usable pressure, and will it arrive safely? This lesson follows the water from the street main to the fixture: the service pipe, its separation from the sewer, the flow and pressure each fixture needs, the valve that caps building pressure, and the shutoff valves an inspector expects to find. Lesson 7 continues with hot water circulation and protection of the potable supply. The numbers are model code numbers; Houston enforces the Uniform Plumbing Code, so confirm the adopted code first.
Any structure with plumbing fixtures that people occupy or live in must have a potable water supply in the amounts and pressures the chapter sets (602.1). Only potable water may serve fixtures used for drinking, bathing, cooking, or for processing food, medical, or pharmaceutical products, and unless the code says otherwise, potable water serves every fixture (602.2). The water service pipe is sized to deliver the required quantities at the required pressures and may not be smaller than 3/4 inch in diameter (603.1).
A water service may share a trench with the building sewer only if the sewer is made of a material listed in Table 702.2. Otherwise the two are kept at least 5 feet apart horizontally, in undisturbed or compacted earth. The 5-foot rule does not apply at a crossing if the service is sleeved to at least 5 feet on each side of the sewer centerline, or if the bottom of the service within 5 feet of the sewer is at least 12 inches above the top of the sewer. A potable service may never run in, under, or above a cesspool, septic tank, drainage field, or seepage pit (603.2.1). Every yard rehab that trenches a new service beside an old sewer lateral of unknown material meets this rule.
The distribution system is designed so that, at peak demand, each fixture supply outlet delivers at least the flow rate and flow pressure in Table 604.3 (604.3). The pressure column is what matters at the meter: it is the pressure that must remain at the outlet after friction and elevation are subtracted. Design uses the lowest street pressure the main ever shows (604.6). Where the street cannot deliver the Table 604.3 pressures, a booster system is required (604.7).
| Fixture supply outlet | Flow, gpm | Pressure, psi |
|---|---|---|
| Lavatory, private | 0.8 | 8 |
| Lavatory, public | 0.4 | 8 |
| Shower, ordinary valve | 2.5 | 8 |
| Shower or bathtub with a balanced-pressure or thermostatic valve | 2.5 or 4 | 20 |
| Water closet, tank type or flushometer tank | 1.6 to 6 | 20 |
| Urinal, valve | 12 | 25 |
| Water closet, flushometer valve (siphonic / blowout) | 25 | 35 / 45 |
Where pressure in the building exceeds 80 psi static, an approved pressure-reducing valve with a strainer must reduce it to no more than 80 psi static (604.8). Two exceptions exist: service lines to sill cocks and outside hydrants, and main risers, where the pressure is brought to 80 psi or less at the individual fixtures. The valve is designed to stay open if it fails, so a failed valve delivers full main pressure rather than no water (604.8.1). The valve and strainer must be arranged so parts can be repaired or removed without cutting the line or taking the valve out (604.8.2).
Worked example: a restaurant sits on a main that measures 95 psi static. The building distribution exceeds 80 psi, so a valve and strainer are required, set at or below 80 psi static. A flushometer closet needs 35 to 45 psi at the fixture, so with the valve set at 80 psi the design has up to 35 psi to lose to friction and elevation before a blowout flushometer closet drops below its 45 psi. If the main showed only 30 psi at peak, a booster system would be required for flushometer fixtures (604.7).
Where the main cannot supply the minimum pressures and quantities, the supply is supplemented by an elevated tank, a hydropneumatic system, or a booster pump (606.5.1). Every booster pump needs a low-pressure cutoff that protects the suction side from a vacuum when suction pressure falls to 10 psi or less (606.5.5).
A fixture supply pipe ends no more than 30 inches from its connection to the fixture and extends to the adjacent floor or wall. Table 604.5 gives the minimum sizes. Note how large the flushometer closet supply is.
| Fixture | Minimum supply pipe |
|---|---|
| Lavatory, flush-tank water closet, drinking fountain | 3/8 in |
| Kitchen sink, bathtub, single shower head, service sink, hose bibb | 1/2 in |
| Urinal, flushometer valve | 3/4 in |
| Water closet, flushometer valve | 1 in |
At summary level: pipe and fittings in the water supply may contain no more than 8 percent lead, and those supplying drinking or cooking water must meet a weighted average of 0.25 percent or less (605.2). Underground service pipe must be listed for potable use and rated for at least 160 psi (605.3). Piping may not be installed in soil or groundwater contaminated with solvents or fuels, and a chemical analysis is required where that is suspected (605.1). Where quick-closing valves are used, a water hammer arrestor is required (604.9).
Full-open valves belong on the service near the curb, on the discharge side of every meter, at the entrance to the structure (one for each tenant in a multi-tenant building), at the base of most risers, on the water supply to every water heater, and to tanks (606.1). Shutoff valves belong at each fixture supply, each sillcock, and each appliance (606.2). All of these valves need access (606.3), and service and remote valves must be identified (606.4).
In the field
In a three-tenant strip center rehab, the owner asks the contractor to swap out an old meter and tie the new service to the existing risers. Confirm that each tenant has its own shutoff valve where the branch enters the space, that the meter has a valve on its discharge side, and that the PRV and its strainer can be serviced without cutting the line. Ask what the street pressure reads: a static reading over 80 psi at the meter means a PRV is required, and a low reading may mean a flushometer closet will never flush well.
Set the service pipe, its distance from the sewer, the pressures and the supply stub-out, and see what an inspector would pass or fail. Open it in its own window.
1. A designer for a Group B office shows a 1/2-inch water service pipe from the meter to the building. What is the finding under 2021 IPC Section 603.1?
2. A new water service is laid in the same trench as an existing building sewer of a material that is not listed in Table 702.2, at a Group R-2 site. What separation does Section 603.2 require?
3. A water service crosses over a building sewer at a Group B site. The bottom of the service pipe is 14 inches above the top of the sewer within 5 ft of the crossing. Under Section 603.2, the sleeve requirement:
4. A rural rehab plans to run a new potable water service across a septic tank drainage field. What does Section 603.2.1 say?
5. A Group R-2 apartment building has a static pressure of 92 psi at the entrance to the building water distribution piping. What does Section 604.8 require?
6. A Group A-3 pool building has a hose bibb line that runs ahead of the pressure-reducing valve at 90 psi static. What does the exception to Section 604.8 say?
7. What must a pressure-reducing valve do if it fails, according to Section 604.8.1?
8. A design calculation for a Group A-3 community hall shows 30 psi left at a siphonic flushometer valve water closet at peak demand. What does Table 604.3 conclude?
9. On the top floor of a Group R-2 building, a design shows 15 psi remaining at close-coupled tank water closets at peak demand. What is the finding?
10. A Group B high-rise design needs a water pressure booster pump. What low-pressure protection does Section 606.5.5 require on the pump?
11. A Group A-4 locker room uses flushometer-valve water closets. What is the smallest fixture supply pipe permitted by Table 604.5?
12. An inspector finds a lavatory supply stub-out that ends 40 inches from the lavatory, with flexible connectors made up at the fixture. Under Section 604.5, the supply pipe:
13. A three-tenant Group M strip center has a common water supply system. What does Section 606.1 require at each tenant space?
14. A contractor in a Group R-2 building is laying new underground water service pipe outside the structure. What minimum working pressure rating does Section 605.3 require at 73.4 degrees F?